Kabel Bundel Udara MV ABC Standar AS/NZS 3599

Kabel Bundel Udara MV ABC Standar AS/NZS 3599

Spesifikasi:

    AS/NZS 3599 minangka seri standar kanggo kabel bundel udara tegangan menengah (MV) (ABC) sing digunakake ing jaringan distribusi overhead.
    AS/NZS 3599—Kabel listrik—Dibundel antena—Diisolasi polimer—Tegangan 6,3511 (12) kV lan 12,722 (24) kV
    AS/NZS 3599 nemtokake syarat desain, konstruksi, lan pengujian kanggo kabel kasebut, kalebu bagean sing beda kanggo kabel sing dilindungi lan ora dilindungi.

Rincian Cepet

Tabel Parameter

Aplikasi:

Kabel udara tegangan menengah utamane digunakake kanggosaluran udara sekundering tiang utawa minangka pakan menyang bangunan omah.

asd
asd

Standar:

AS/NZS 3599---Kabel listrik—Dibundel antena—Diisolasi polimer—Tegangan 6,3511 (12) kV lan 12,722 (24) kV

Tegangan:

6.6kV-22kV

Konstruksi:

Layar Konduktor: Lapisan semi-konduktif sing diekstrusi.
Isolasi: XLPE
Layar Isolasi: Lapisan semi-konduktif sing diekstrusi.
Layar Logam (opsional): Layar kawat tembaga utawa layar pita tembaga.
Pamisah: Pita semi-konduktif sing bisa ngembang.
Selubung njaba: HDPE.
Konduktor Pendukung:Kawat baja galvanis.
Perakitan Telung inti layar berinsulasi XLPE dibundel ing sekitar kabel baja galvanis ing lay sisih tengen.

asd

Apa sebabe milih kita?

Kita ngasilake kabel kualitas dhuwur kanthi nggunakake bahan-bahan berkualitas tinggi:

Apa Sebab Milih Kita (2)
Apa Sebab Milih Kita (3)
Apa Sebab Milih Kita (1)
Apa Sebab Milih Kita (5)
Apa Sebab Milih Kita (4)
Apa Sebab Milih Kita (6)

Tim pengalaman sing sugih ngerti apa sing dikarepake:

1212

Pabrik kanthi fasilitas lan kapasitas sing apik kanggo njamin pangiriman tepat wektu:

1213

AS/NZS 3599 bagean 1 6.35/11kV AL/XLPE/HDPE kabel tanpa saringan

Cacahing Inti x Penampang Nominal

Konduktor Fase

Unit Suspensi Messenger

Area Penampang Nominal

Beban Pecah

Diameter Konduktor

Kekandelan Isolasi

Kekandelan Layar Isolasi

Kekandelan Selubung

Kandas

No.×mm²

mm

mm

mm

mm

No.×mm

mm²

kN

3×35 6.9 3.4 0.8 1.2 7/4.75 52.4 1370
3×50 8.1 3.4 0.8 1.2 7/4.75 54.6 1530
3×70 9.7 3.4 0.8 1.2 7/4.75 57.8 1790
3×95 11.4 3.4 0.8 1.2 7/4.75 61.3 2100
3×120 12.8 3.4 0.8 1.2 19/3.50 67.3 2540
3×150 14.2 3.4 0.8 1.2 19/3.50 70.1 2840
3×185 15.7 3.4 0.8 1.2 19/3.50 73.1 3190

 

Kabel AS/ZNS 3599 bagean 1 6.35/11kV AL/XLPE/CWS/HDPE sing disaring

Cacahing Inti x Penampang Nominal

Diameter Konduktor

Kekandelan Isolasi

Kekandelan Layar Isolasi

Kawat Tembaga Layar Stranding

Kekandelan Selubung

Kawat Baja Galvanis Teruntai

Area Penampang Nominal

Beban Pecah

No.×mm²

mm

mm

mm

No.×mm

mm

No.×mm

mm²

kN

Layar tugas entheng
3×35 6.9 3.4 0.8 25/0.85 1.8 7/2.00 54.1 1820
3×35 6.9 3.4 0.8 25/0.85 1.8 19/2.00 58.1 2130
3×50 8.1 3.4 0.8 25/0.85 1.8 19/2.00 60.4 2300
3×70 9.7 3.4 0.8 25/0.85 1.8 19/2.00 63.6 2570
3×95 11.4 3.4 0.8 25/0.85 1.8 19/2.00 67.0 2900
3×120 12.8 3.4 0.8 25/0.85 1.8 19/2.00 69.8 3190
3×150 14.2 3.4 0.8 25/0.85 1.9 19/2.00 73.0 3530
3×185 15.7 3.4 0.8 25/0.85 1.9 19/2.00 76.0 3890
Layar tugas berat
3×35 6.9 3.4 0.8 40/0.85 1.8 7/2.00 54.1 2050
3×35 6.9 3.4 0.8 40/0.85 1.8 19/2.00 58.1 2360
3×50 8.1 3.4 0.8 23/1.35 1.8 19/2.00 62.4 2820
3×70 9.7 3.4 0.8 32/1.35 1.8 19/2.00 65.6 3440
3×95 11.4 3.4 0.8 39/1.35 1.8 19/2.00 69.0 4030
3×120 12.8 3.4 0.8 39/1.35 1.8 19/2.00 71.8 4320
3×150 14.2 3.4 0.8 39/1.35 1.9 19/2.00 75.0 4670
3×185 15.7 3.4 0.8 39/1.35 1.9 19/2.00 78.0 5020

 

AS/NZS 3599 bagean 1 12.7/22kV AL/XLPE/HDPE kabel tanpa saringan

Cacahing Inti x Penampang Nominal

Konduktor Fase

Unit Suspensi Messenger

Area Penampang Nominal

Beban Pecah

Diameter Konduktor

Kekandelan Isolasi

Kekandelan Layar Isolasi

Kekandelan Selubung

Kandas

No.×mm²

mm

mm

mm

mm

No.×mm

mm²

kN

3×35 6.9 5.5 0.8 1.2 7/4.75 61.0 1780
3×50 8.1 5.5 0.8 1.2 7/4.75 63.3 1970
3×70 9.7 5.5 0.8 1.2 7/4.75 66.5 2260
3×95 11.4 5.5 0.8 1.2 7/4.75 69.9 2600
3×120 12.8 5.5 0.8 1.2 19/3.50 75.9 3070
3×150 14.2 5.5 0.8 1.2 19/3.50 78.7 3390
3×185 15.7 5.5 0.8 1.2 19/3.50 81.7 3760

 

Kabel sing disaring AS/NZS 3599 bagean 1 12.7/22kV AL/XLPE/CW/HDPE

Cacahing Inti x Penampang Nominal

Diameter Konduktor

Kekandelan Isolasi

Kekandelan Layar Isolasi

Kawat Tembaga Layar Stranding

Kekandelan Selubung

Kawat Baja Galvanis Teruntai

Area Penampang Nominal

Beban Pecah

No.×mm²

mm

mm

mm

No.×mm

mm

No.×mm

mm²

kN

Layar tugas entheng
3×35 6.9 5.5 0.8 25/0.85 1.8 7/2.00 62.7 2280
3×35 6.9 5.5 0.8 25/0.85 1.8 19/2.00 66.7 2580
3×50 8.1 5.5 0.8 25/0.85 1.8 19/2.00 69.0 2780
3×70 9.7 5.5 0.8 25/0.85 1.9 19/2.00 72.6 3110
3×95 11.4 5.5 0.8 25/0.85 1.9 19/2.00 76.0 3460
3×120 12.8 5.5 0.8 25/0.85 2.0 19/2.00 79.2 3810
3×150 14.2 5.5 1.0 25/0.85 2.0 19/2.00 82.8 4230
3×185 15.7 5.5 1.0 25/0.85 2.1 19/2.00 86.2 4650
Layar tugas berat
3×35 6.9 5.5 0.8 40/0.85 1.8 7/2.00 62.7 2510
3×35 6.9 5.5 0.8 40/0.85 1.8 19/2.00 66.7 2810
3×50 8.1 5.5 0.8 23/1.35 1.8 19/2.00 71.0 3300
3×70 9.7 5.5 0.8 32/1.35 1.9 19/2.00 74.6 3970
3×95 11.4 5.5 0.8 39/1.35 1.9 19/2.00 78.0 4600
3×120 12.8 5.5 0.8 39/1.35 2.0 19/2.00 81.2 4950
3×150 14.2 5.5 1.0 39/1.35 2.0 19/2.00 84.8 5360
3×185 15.7 5.5 1.0 39/1.35 2.1 19/2.00 88.2 5790

 Data teknis

Penampang Nominal

Rating Arus Terus-terusan

Udara Tenang

Angin 1m/s

Angin 2m/s

mm² A A A
35 105 145 165
50 125 170 200
70 150 215 250
95 180 260 300
120 205 300 350
150 230 340 395
185 265 390 450